根据搜索结果,通风管道法兰的铆钉间距有以下规定:
According to the search results, there are the following regulations for the rivet spacing of ventilation duct flanges:
69计划房彩票对于一般情况,微、低压和中压系统风管法兰的螺栓及铆钉的间距应小于或等于150mm;高压系统风管则应小于或等于100mm。
For general situations, the spacing between bolts and rivets of air duct flanges for micro, low, and medium pressure systems should be less than or equal to 150mm; The air duct of the high-pressure system should be less than or equal to 100mm.
空气洁净度等级为N1级至N5级时,风管法兰的螺栓及铆钉孔的间距不应大于80mm;当空气洁净度等级为N6级至N9级时,不应大于120mm。
69计划房彩票When the air cleanliness level is N1 to N5, the spacing between the bolt and rivet holes of the air duct flange should not exceed 80mm; When the air cleanliness level is N6 to N9, it should not exceed 120mm.
柔性管与法兰组装时,铆钉间距为60~80mm。
When assembling flexible pipes with flanges, the distance between rivets should be 60-80mm.
69计划房彩票铆接应牢固,铆钉间距宜为100mm~120mm,且数量不少于4个。
69计划房彩票Riveting should be firm, with a spacing of 100mm to 120mm between rivets, and the quantity should not be less than 4.
69计划房彩票这些规定确保了通风管道法兰连接的强度和密封性,根据不同的系统压力和空气洁净度等级,铆钉间距有所不同
69计划房彩票These regulations ensure the strength and sealing of ventilation duct flange connections, and the rivet spacing varies depending on the system pressure and air cleanliness level